Inquiry (采购产品): Searc for Starter WASA is in search of the 2 of the following items available exstock for delivery next week. If they are available, what is the price? 415 volt, 60 hertz, 250 hp autotransformer motor control centre ganged together with common bus bars and 600 amp main circuit breaker. Both motors shall be outfitted with a 400 amp circuit breaker, Symcom motor saver 777 voltage/current monitor and autotransformer configured in the starter to the 60 % tap of the autotransformer for the starting circuit. The autotransformer shall also have terminal protection, incorporated in the control circuit of each motor starter, and antihunt timers in the respective instrument control circuit for automatic control via both suction and discharge pressure switches. The control circuits shall also provide incomplete sequence timers for protection for the autotransformer. Annamay Haynes **** Hidden Message ***** Annamay Haynes Farm Road Valsayn St Joseph99999 TTO Company: Water and Sewerage Authority of Trinidad and Tobago Title: General Manager - Corporate Services Phone: 1868-620-4219 Fax: 1868-662-4245 E-mail: ahaynes@wasa.gov.tt **** Hidden Message ***** ahaynes@wasa.gov.tt