详细内容 - Protective Item Trip Time - Over-current DEF : 0.2~30sec INV : 1~30 - Undercurrent 0.5~30 sec - Phase Loss within 3 sec - Phase Unbalance within 8 sec - Phase Reversal 0.1~0.3 sec - Locked Rotor Lock : within 0.5sec after D-time(in DEF set)- Stall : 0.05 ~ 10sec (in DEF set) - Compact Design - MCU( Microprocessor Control Unit ) Based - Three Integral Current Transformers - Multiple Protection Functions - Digital Ammeter/3 Phase Current Display - Troubleshooting/Trip Cause Memory, Display - Adjustable Operating Features by Mode switch - Wide Current Adjustment Range - Selectable Time-Current Characteristics(Inverse/Definite) - Manual(Instantaneous)/Electrical(Remote)Reset - Test Function - Ambient Insensitive - Selectable Fail-safe and Non-fail-safe Operation Modes - Inverter (20~400Hz) - EOCR-3DE : Panel Mounting type - EOCR-FDE : Flush Mounting type(Display) 联系方式 Email plank@plank.com.tw 公司名 CAVIAR PETROSSIAN 国家 法国 联系人 M PETROSSIAN ARMEN 地址 18 BOULEVARD DE LA TOUR MAUBOURG, 75007, PARIS 电话 0033 1 44896768 **** Hidden Message *****Email dadaltd@superonline.com,merisen@ixir.com,sizzlimgkrafts@yahoo.com,steve@overbreak.com,eveicnal@ms31.hinet.net,
|