Inquiry (采购产品): RFQ: VOGTLE NUCLEAR I need a quote for the following two transformers by Tuesday 6/20/06. Transformer Type: Oil Filled KVA: 8570 Phases: Three (3) Frequency: 60 Conductor: Copper Primary/Secondary Winding BIL: 150kV/30kV Primary/Secondary Voltage: 25000/895 delta/wye Cooling AA Temperature Rise: 55° C Ambient Temperature: 40° C Impedance: 6% Nominal Efficiency: Greater than 98% Insulation: NA Overload: 150% for 30 seconds Electrostatic Shield Primary to Secondary Yes Analog Temperature Indication / Alarm / Trip (49) Device Yes Duty Exciter Duty/Non linear load Taps None Primary CT’s 3 – 300:5 (C200) wired to shorting terminal strip Secondary CT’s 3 – 9000:5 (C200) wired to shorting terminal strip Primary Termination Isophase Bus Secondary Termination Isophase Bus Over Pressure Trip(63) Device Yes **** Hidden Message ***** SAM MOSES 1 RIVER RD. BLDG. 40, 5TH FLOOR, D04 SCHENECTADY, NY 12345 USA Company: GENERAL ELECTRIC Title: BUYER Phone: 518-385-1934 E-mail: sam.moses@ge.com **** Hidden Message ***** sam.moses@ge.com