Inquiry (采购产品): Air cooled water chiller 1) Duty : Continuous. Chilled water required at 15 deg. C. The return from the system is at 23 deg. C. You can consider start up water temperature as 35 deg. C. The distance between chiller and user is approximately 10m. ?” size pipe is adequate. You may consider standard pipe size. Material of construction of pipe can be Carbon steel-insulated. 2) Flow rate required is 20 gph. 3) The system is closed loop. 4) It shall be a skid mounted unit suitable for out door, unsheltered installation with its self sufficient local control panel. the panel shall include starters for all the drives. Hazardous area classification is Zone 2, IIB, T3. The maximum ambient temperature is 50 deg. C, minimum ambient temperature is 4 deg. C. Consider saline dusty environment. Epoxy painting with minimum dry film thickness of 230 micrometer shall be considered. 5) The unit shall be air cooled type, since cooling water is not available for this project. **** Hidden Message ***** Pravin Parchure C/O Petrofac house, Al soor street, Pin 23467, Sharjah, UAE Sharjah, GA 23467 AFG Company: Petrofac International Ltd. Title: Rotating Equipment Engineer Phone: 00971 6 5740999 E-mail: parchurp@petrofac.co.ae **** Hidden Message ***** parchurp@petrofac.co.ae